Step by step guide to phase initialization on the
Navigator and Pilot motion processors
| History |
|
|
|
| Date |
Version |
Author |
Notes |
2001-05-18 |
1.0.0 |
JJ |
First version |
2001-05-23 |
1.0.1 |
JJ |
Updated with input from engineering |
2001-05-29 |
1.0.2 |
JJ |
Added info on PWM active state |
This document describes in detail the setup procedure for initializing
commutation on the
brushless Navigator and Pilot families of motion processors. You should
read this entire
document before attempting the initialization procedure for the first
time. It is assumed that you
have read the Sinusoidal Commutation section of the User’s Guide
prior to reading this
document.
When controlling a brushless motor, an initial phase angle must be determined
before the
motor can be rotated. The PMD brushless motion processors provide several
methods for
phase initialization. This document describes the Algorithmic and Hall-based
methods.
Phase initialization must be performed whenever the motion processor is
reset. This document
will help you determine the correct sequence of commands to execute. This
process is
performed once after a hardware or software reset for every brushless
axis that is controlled by
the motion processor.
All commands are presented in a generic format that indicates a command
name and optional
parameters. You should use the commands in a format that is appropriate
for the software you
are using. For a detailed explanation of command format, refer to the
Programmer’s
Reference. In this document all numbers prefixed with “0x”
are presented in hexadecimal
notation.
Before attempting to initialize using any of the presented methods,
input and output must be
checked.
For information on pin and signal connections, refer to your motion
processors Technical
Specifications manual or the appropriate Developer’s Kit manual.
You should have an encoder connected to your motion processor, preferably
one that provides
an index signal once per rotation. Your motion processors’ Technical
Specifications manual
has details on the required timing of the index signal and the way in
which it is gated with the
channel A and channel B signals. The index signal is used for correcting
any commutation
error caused by either lost encoder counts or a non-integer phase count
value. This is
discussed later.
While rotating the motor/encoder, execute the command GetActualPosition.
The returned
value should increment when rotating in one direction, and decrement when
the rotating in the
opposite direction. On the Navigator family you can also use the command
GetSignalStatus to
monitor the state of the encoder A, B and Index signals. The Pilot family
does not support this
feature.
You can also test the Index signal by issuing the command GetCaptureValue.
When the
encoder is rotated, GetCaptureValue should return a value once per rotation
that is
incrementing or decrementing by a value that is equal to the number of
encoder counts per full
rotation.
- GetActualPosition oscillates between 0 and 1
- One of the encoder A or B signals is not connected correctly.
Check these
connections as well as GND and +5V supply to your encoder.
- The encoder A and B signals must be 90 degrees out of phase for
quadrature
decoding to operate correctly. Verify this using an oscilloscope.
- Index capture does not work
- The index signal is gated with the A and B encoder signals. This
requires that all
signals must be ‘active’ for a capture to occur. The
index signal is expected to
be active LOW by default. If it is not, the command SetSignalSense
can be used
to change its active state to be HIGH. NOTE: Care must be taken
when
inverting an A or B channel signal since this may violate the signal
state required
for an index capture.c
Even before the phasing is correctly initialized, the motion processor
can generate motor output
signals that can be checked. The amplifier output signals should
not be connected to the
motor during this test.
The following sequence of commands will generate amplifier output when
the motor/encoder is
rotated manually.
SetOutputMode m |
// m is 0 for DAC, 1 for PWM S/M and 2 for PWM 5050 |
SetNumberPhases x |
// x is 2 or 3 depending on type of motor |
SetPhaseCounts 1024 |
// # of encoder counts per electrical cycle |
SetMotorMode 0 |
// places axis in open loop mode |
SetMotorCommand 16384 |
// This value specifies the magnitude of the sinusoidal waveform
motor
command. A value from 0 to 32,767 represents 0->100% of full-scale
output.
16384 represents 50%. |
The encoder should be connected to the motion processor and functioning
correctly. Connect
the output signals from either the motion processor or amplifier to an
oscilloscope. Rotate the
motor/encoder and the output signals from the motion processor/amplifier
will fluctuate in a
sinusoidal fashion. This confirms that your output is operational.
If you are using PWM output, check the ‘active’ interpretation
that your amplifier expects. Refer
to the User’s Guide for details on the format and encoding of this
signal.
To perform sinusoidal commutation it is necessary to specify the number
of encoder counts per
electrical cycle. To determine this value the number of electrical cycles
of the motor and the
number of encoder counts per motor revolution must be known. Knowing these
two quantities,
the number of encoder counts per electrical cycle is given by the following
equation:
Counts_per_cycle = Counts_per_rot/Electrical_cycles
where:
Counts_per_rot is the number of encoder counts per motor rotation
Electrical_cycles is the number of motor electrical cycles per rotation
The number of electrical cycles can normally be determined by examining
the motor
manufacturer’s specification. The number of electrical cycles is
usually half the number of
poles. Care should be taken not to confuse poles with pole pairs. If pole
pairs are specified,
then take this to mean the number of electrical cycles.
The command used to set the number of encoder counts per electrical
cycle is
SetPhaseCounts. To read back this value use the command GetPhaseCounts.
To enhance long term commutation reliability the PMD motion processors
provides the ability to
utilize an index pulse input from the motor encoder as a reference point
during commutation.
By using an index pulse during the phase calculations any long-term loss
of encoder counts,
which might otherwise affect the accuracy of the commutation, are automatically
eliminated.
To utilize index pulse referencing the motor encoder chosen must provide
an index pulse signal
to the chipset once per rotation. This index pulse is connected to the
chipset using the Index
signal. For information on pin and signal connections, refer to your motion
processors
Technical Specifications manual or the appropriate Developer’s
Kit manual.
Index pulse referencing is recommended for all rotary brushless motors
with quadrature
encoders. For linear brushless motors it is generally not used, although
it can be used as long
as the index pulses are arranged so that each pulse occurs at the same
phase angle within the
commutation cycle.
When using an index pulse the number of encoder counts per electrical
cycle is not required to
be an exact integer. In the case that this value is not an integer, the
nearest integer should be
chosen. Conversely, if index pulses are not being used then the number
of counts per electrical
cycle must be an exact integer, with no remainder. For example if a 6-pole
brushless motor is
to be used with an encoder without an index pulse than an encoder with
1200 counts per
rotation would be an appropriate choice, but an encoder with 1024 would
not because 1024
cannot be divided by 3 evenly.
The command SetPhaseCorrectionMode is used to enable/disable index pulse
phase
correction.
If the motor has hall signals and they are 120 degrees apart, then hall-based
initialization is the
best method to use. This is because it requires no initial motor rotation
for phasing to be
determined. However, as a first step it can often be easiest to use the
algorithmic method just
to verify your connections and to establish motor rotation. Algorithmic
can also be used to
obtain a reference point for verifying the hall initialization. This is
discussed later.
If you do not have hall sensors, algorithmic initialization should be
used. Other methods are
also available. These are discussed in the User’s Guide sinusoidal
commutation section.
In the algorithmic initialization mode no additional motor sensors beyond
the position encoder
are required. To determine the phasing the chipset performs a sequence
that briefly stimulates
the motor windings, and sets the initial phasing using the observed motor
response. From the
resulting motion the chipset can automatically determine the correct motor
phasing.
Depending on the size and speed of the motor, the time between the start
of motor phasing and
the motor coming to a complete rest (settling time) will vary. To accommodate
these
differences the amount of time to wait for the motor to settle is programmable
using the
command SetPhaseInitializeTime. To read back this value use the command
GetPhaseInitializeTime.
To minimize the impact on the system mechanics this method utilizes a
motor command value
set by the host processor to determine the overall amount of power to
"inject" into the motor
during phase initialization. Typically, the amount of power to inject
should be in the range of 5 -
25 % of full-scale output, but in any case should be at least 3 times
the breakaway starting
friction. For best results the initialization motor command value should
be determined
experimentally. The command used to set the motor output level is SetMotorCommand.
To
read back this value use the command GetMotorCommand.
To execute the initialization procedure, the command InitializePhase
is used. Upon executing
this command, the phasing procedure will immediately be executed.
- Perform Initialization
Shown below is a typical sequence of commands to perform the initialization.
SetOutputMode m |
// m is 0 for DAC, 1 for PWM S/M and 2 for PWM 5050 |
SetNumberPhases x |
// x is 2 or 3 depending on type of motor |
SetPhaseCounts yyyy |
// yyyy is # of encoder counts per electrical cycle |
SetPhaseInitializeMode 0 |
// set phase initialize mode to 'algorithmic' |
SetMotorMode 0 |
// places axis in open loop mode, required for algorithmic initialization. |
SetPhaseInitializeTime zzzz |
// zzzz is # of motion processor cycles to initialize for |
SetMotorCommand wwww |
// wwww is motor command. |
| InitializePhase |
|
During algorithmic phase initialization the motor may move suddenly
in either direction. Proper
safety precautions should be taken to prevent damage from this movement.
In addition, to provide
accurate results motor movement must be unobstructed in both directions
and must not experience
excessive starting friction.
As stated previously, the value used for the motor command should be
between and 5-25% of
full-scale output. Start at a value 1000 and work up slowly until you
see motion occur. You can
start with a value of 3,000 – 5,000 for the SetPhaseInitializeTime.
The exact time required is
determined experimentally and is the time it takes for the motor to
“settle” between excitation
cycles.
Once the above sequence has been issued, the motor will perform 2 short
movements. The
amount of rotation of each move is dependant upon the electrical characteristics
of the motor.
Before attempting any further controlled motion, the host software should
issue the command
GetActivityStatus and check for the state of bit 0. When bit 0 returns
1, the chipset has
completed the initialization. Refer to the User’s Guide and Programmer’s
Reference for more
information on this command.
- Check commutation
After phase initialization has been completed it is useful to check
the smoothness of the motor
rotation in open loop mode to verify that the motor phasing initialization
and commutation is
correct. To do this use the following command sequence:
SetMotorMode 0 // set axis for open loop operation
SetMotorCommand xxxx // xxxx is the motor command from 0 to +/-32,767
to output
Update
The 'xxxx' value represents the fraction of the value 32,767 of total
power that will be applied to
the motor. For example a value of 1,000 sends roughly 3 % (1000/32767)
of the total power to
the motor.
When the motor mode is set to off (SetMotorMode 0) the motor
is not under servo control.
Be aware that the motor may spin rapidly after a motor command value
is applied. Use
small values and increase slowly.
After this command sequence the motor should smoothly spin in one direction
or the other. The
motor command is a signed number and the sign controls the rotation
direction. When a
positive motor command is given the motor should rotate in the positive
(increasing encoder
counts) direction. Verify this using the command GetActualPosition.
The motor should rotate at
approximately the same speed in both directions when given the same
motor command
magnitude. For example, SetMotorCommand –2000 and SetMotorCommand
+2000 should
result in motion at approximately the same speed in both directions.
If the motor spins roughly,
in the wrong direction, or if it moves a short distance and then abruptly
stops there may be a
problem with the commutation. See the troubleshooting notes below and
re-test.
Once the motor is spinning smoothly in both directions under open loop
control, re-enable
closed-loop servo control by executing the command SetMotorMode On.
Troubleshooting
When performing algorithmic initialization there are 2 potential causes
of problems. Depending
on the nature of the problem, either or both of the following changes
will be required.
- Encoder counting direction is incorrect. When the motor windings
are energized for
positive direction rotation, the motion processor expects an incrementing
encoder count.
If this is not the case initialization will not succeed. The motor
can lock or behave in an
uncontrolled fashion. To solve this problem the counting direction
must be reversed.
This can be achieved by using the command SetSignalSense to invert
one of the
encoder channels. If you intend to use the automatic phase correction
feature
(SetPhaseCorrectionMode), care must be taken as inverting an encoder
signal may
prevent index captures from occurring. The direction can also be
reversed by swapping
the connection of A+/A- signals for a differential encoder or by
swapping the connection
of the A and B signals for a single ended encoder.
- The motor windings are out of sequence. If the motor winding connections
are not in
the correct sequence there will be no motion during the initialization
process. In a 2
phase motor, swapping the phase A and B connections results in the
motor rotating in
the opposite direction. It is identical to reversing the encoder
counting direction. In a 3
phase motor, reversing either A and B, or B and C will correct an
out of order connection
sequence.
After attempting the above changes you must re-run the initialization
procedure and re-check
the commutation. When operation appears correct you can move onto
the next step.
- Set Filter Parameters
For motion to occur, some amount of feedback gain must be specified.
Initially use just a
proportional gain (Kp) with a very low value between 1 and 25. Later
you can add integral or
derivative gains as well as feedforward gains if desired. The following
sequence shows how to
set the P, I, and D terms of the filter and how to 'update' them, making
them active.
SetKp xxxx |
// xxxx is the desired proportional gain |
SetKd yyyy |
// yyyy is the desired derivative gain |
SetKi zzzz |
// zzzz is the desired integral gain |
SetIntegrationLimit aaaa |
// aaaa is the desired integration limit |
Update |
// make thee values active. |
It is not necessary to specify all 3 gains. Just Kp, followed by an
Update can be specified
initially. Kd and Ki are optional.
When exercising the motor use extreme caution. It is the responsibility
of the user to
observe safety precautions at all times.
At this stage, if a force is applied to the motor shaft it should respond
by attempting motion in
the opposite direction, thereby attempting to maintain it’s initial
position. If this is not the case
go back and re-check commutation, making certain that the positive encoder
counting direction
and the motor positive rotation direction are the same.
- Make a Trajectory Move
To test that the motor is being driven properly, set up and execute
a small trapezoidal move.
Specify a small distance of (for example) 5,000 counts, and a low velocity
and acceleration of
(for example) 10,000, and 10 respectively. With a cycle time of 153
µsec, these values
correspond to roughly 997 counts/sec, and 6516 counts/sec2,
respectively.
Whatever profile values you use, be sure that they are safe
for your system.
Here is the command sequence to use:
SetProfileMode 0 |
// Sets current profile mode to trapezoidal |
SetPosition 5000 |
// 5000 is the desired destination position |
SetVelocity 10000 |
// 10000 is the desired maximum velocity |
SetAcceleration 10 |
// 10 is the desired acceleration |
SetDeceleration 10 |
// 10 is the desired deceleration |
Update |
// execute the move |
After entering this sequence of commands you should see the axis smoothly
move for about 6
seconds if the suggested values are used and the cycle time of the motion
processor is 153
µsec.
If you do not see the axis moving, or if the axis jumps rapidly in one
direction or the other, there
may be a problem with the board or software settings. Re-check and review
the setup
procedures, as well as the parameter settings.
- Initialization complete
When the initialization sequence is repeated, the results should be
consistent. If they are not
the initialization may not be correct. Re-check and contact PMD if problems
persist.
If you do not have hall sensor signals, initialization is complete.
Record the steps followed and
incorporate them into your host processor initialization sequence.
Collecting information helpful for Hall-based initialization
Assuming that you have an index signal present, complete the initialization
procedures and
program motion that results in at least full rotation of the motor in
either direction. After this
execute the command GetPhaseOffset and record the result. Repeat this
5 times. The value
returned by GetPhaseOffset should be within the same range for successive
trials. If it is not
refer to the above trouble-shooting sections. This value will be used
later to verify a successful
hall-based initialization since this reference data should be approximately
the same with both
initialization methods. It is the location of the start of the first
electrical cycle of phase A with
respect to the index signal.
Hall-based Initialization
To set the chipset for Hall-based initialization use the command SetPhaseInitializeMode
and
specify Hall-based as the parameter. In this mode 3 Hall-Sensor signals
are used to initially
determine the motor phasing, and sinusoidal commutation begins automatically
after the motor
has moved through one full rotation.
The Hall-Sensor signals are fed back to the chipset through the signals
Hall1A-C (axis #1) and
Hall2A-C (axis #2), etc. Care should be taken to connect these sensors
properly. To read the
current status of the hall sensors use the command GetSignalStatus.
The following diagram shows the relationship between the state of the
three Hall sensor inputs
for each axis and the commutated motor outputs. This graph shows the
expected Hall sensor
states and winding excitation for forward motion (increasing position).

Unlike the algorithmic method, using Hall-based phase initialization
no special motor setup
procedures is required. Initialization is performed using the command
InitializePhase, and
occurs immediately, without any motor motion.
To accommodate varying types of Hall sensors, or sensors that contain
inverter circuitry, the
signal level/logic interpretation of the Hall sensor input signals can
be set through the host.
The command SetSignalSense accepts a bit-programmed word that controls
whether the
incoming Hall signals are interpreted as active high or active low.
To read back this Hall
interpretation value use the command GetSignalSense. For details on
the programming of this
control word see the Programmer’s Reference manual.
Hall-based initialization should only be used with a 3-phase commutation
waveform, and with Hall
sensors located 120 degrees apart. Hall-sensors located 60 degrees apart
should not be used.
It is imperative that the hall signals are as noise free as possible
and provide a strong ground and
+5V signal to the motion processor inputs.
- Verify the hall sensor connection
The following can be performed without power being applied to the motor/amplifier.
Rotation of
the motor can be done manually.
In addition to connecting the hall sensors to the motion processor,
connect the three hall
signals to an oscilloscope and arrange them as A, B and C as shown above.
The command
GetSignalStatus should be used to verify the correct hall sequence as
outlined above. When
the motor is being manually rotated in a positive direction (the value
returned by
GetActualPosition is increasing), the following sequence should be observed:
6Fx
4Fx
5Fx
57x
77x
67x
The ‘x’ indicates we don’t care about the value of
bits 0-3. The above values are represented in
hexadecimal notation. Since the limit and AxisIn signals are also encoded
in the word returned
by GetSignalStatus, the exact values returned to you may be different.
For example if the limit
signals and AxisIn are LOW, the sequence will look like:
68x
48x
58x
50x
70x
60x
Refer to the Programmer’s Reference description of GetSignalStatus
for a detailed explanation
of the bit encoding.
Troubleshooting
If the above sequence is not observed, you may need to change the hall
wiring. It is wise to
perform any changes to connections in conjunction with an oscilloscope
so that the signal state
can be observed electrically and numerically.
- A hall signal is inverted. Use the command SetSignalSense to invert
the hall sensor that
is in a state opposite to what the motion processor expects.
- One of the hall sensors is out of sequence. Because hall transitions
are expected at
known points within the electrical cycle, the most common problem
is that these
transitions are occurring out of phase. To correct this shift the
connections until the
correct sequence of states as outlined above is observed. If you
reference to one
signal, for example HallA, swapping the connections for signals
B and C should solve
this problem.
- The hall sequence is reversed. If you observe that when the encoder
is counting in an
incrementing fashion the above sequence is reversed, you must reverse
the hall sensor
connections. Swap the hall sensor connections for HallA and HallC.
- Perform Initialization
Once you have verified the hall sensor sequence for positive motor rotation,
execute the
following sequence of commands.
SetOutputMode m |
// m is 0 for DAC, 1 for PWM S/M and 2 for PWM 5050 |
SetNumberPhases x |
// where x is 2 or 3 depending on type of motor |
SetPhaseCounts yyyy |
// yyyy is # of encoder counts per electrical cycle |
SetPhaseInitializeMode 1 |
// set phase initialize mode to 'Hall-based' |
| InitializePhase |
|
Index signal available
At this point there is no requirement to power the motor or amp. The
initialization can be
checked without power.
Rotate the motor at least one turn. Issue the command GetPhaseOffset
and record the result.
If the value returned is 65535, the index signal is not working. Refer
to the start of this
document for more information.
If the value recorded above is approximately equal to the value derived
during algorithmic
phase initialization, than the initialization may be correct. Proceed
to the next step.
If the value is not equal, then it is likely that the hall sensors are
out of phase. Because hall
transitions are expected at known points within the electrical cycle,
the most common problem
is that these transitions are occurring out of phase. To correct an
out of phase problem, rotate
the hall connections and repeat the initialization and test procedure.
That is if the starting
connection sequence is:-
A B C
try
C A B
and
B C A
By using the SetSignalSense command it is also possible to shift the
hall states by 180
degrees. Issue the command SetSignalSense 0x380. 0x380 is a hexadecimal
number. This
inverts the state of all signals, shifting the transition points by
180 degrees.
A combination of both of the above changes may be required in order
to obtain a correct phase
offset reading.
Index signal not available or algorithmic initialization not
performed
If the index signal is not available, initialization must be checked
while there is power applied to
the motor/amplifier.
Proceed to the next step.
- Check commutation
After phase initialization has been completed it is useful to check
the smoothness of the motor
rotation in open loop mode to verify that the motor phasing initialization
and commutation is
correct. To do this use the following command sequence:
| SetMotorMode 0 |
// set axis for open loop operation |
| SetMotorCommand xxxx |
// xxxx is the motor command from 0 to +/-32,767 to output |
| Update |
|
The 'xxxx' value represents the fraction of the value 32,767 of total
power that will be applied to
the motor. For example a value of 1,000 sends roughly 3 % (1000/32767)
of the total power to
the motor.
When the motor mode is set to off (SetMotorMode 0) the motor
is not under servo control.
Be aware that the motor may spin rapidly after a motor command value
is applied. Use
small values and increase slowly.
After this command sequence the motor should smoothly spin in one direction
or the other. The
motor command is a signed number and the sign controls the rotation
direction. When a
positive motor command is given the motor should rotate in the positive
(increasing encoder
counts) direction. Verify this using the command GetActualPosition.
If the motor spins roughly,
in the wrong direction, or if it moves a short distance and then abruptly
stops there may be a
problem with the commutation. See the troubleshooting notes below and
re-test. Once the
motor is spinning smoothly in both directions under open loop control,
re-enable closed-loop
servo control by executing the command SetMotorMode On.
Troubleshooting
When performing hall-based initialization there are 2 potential causes
of problems. Depending
on the nature of the problem, either or both of the following changes
will be required.
- The hall sensors are out of phase. Because hall transitions are
expected at known
points within the electrical cycle, the most common problem is that
these transitions are
occurring out of phase. To correct an out of phase problem, rotate
the hall connections
and repeat the initialization and test procedure. That is, if the
starting connection
sequence is:-
A B C
try
C A B
and
B C A
- When the motor windings are energized for positive direction rotation,
the motion
processor expects an incrementing encoder count. If this is not
the case initialization
will not succeed. The motor can lock or behave in an uncontrolled
fashion. To solve
this problem the counting direction must be reversed. This can be
achieved by using
the command SetSignalSense to invert one of the encoder channels.
If you intend to
use the automatic phase correction feature (SetPhaseCorrectionMode),
care must be
taken as inverting an encoder signal may prevent index captures
from occurring. The
direction can also be reversed by swapping the connection of A+/A-
signals for a differential encoder or by swapping the connection
of the A and B signals for a single ended encoder.
- The motor windings are out of sequence. If the motor winding connections
are not in
the correct sequence there will be no motion during the initialization
process. In a 3
phase motor, reversing either A and B, or B and C will correct an
out of order connection
sequence.
After attempting the above changes you must re-run the initialization
procedure and re-check
the commutation. When operation appears correct you can move onto
the next step.
- Set Filter Parameters
For motion to occur, some amount of feedback gain must be specified.
Initially use just a
proportional gain (Kp) with a very low value between 1 and 25. Later
you can add integral or
derivative gains as well as feedforward gains if desired. The following
sequence shows how to
set the P, I, and D terms of the filter and how to 'update' them, making
them active.
SetKp xxxx |
// xxxx is the desired proportional gain |
SetKd yyyy |
// yyyy is the desired derivative gain |
SetKi zzzz |
// zzzz is the desired integral gain |
SetIntegrationLimit aaaa |
// aaaa is the desired integration limit |
| Update |
// make thee values active. |
It is not necessary to specify all 3 gains. Just Kp, followed by an
Update can be specified, just a
Kd, etc.
When exercising the motor use extreme caution. It is the responsibility
of the user to
observe safety precautions at all times.
At this stage, if a force is applied to the motor it should respond
by attempting motion in the
opposite direction, thereby attempting to maintain it’s current
position. If this is not the case go
back and re-check commutation, making certain that the positive encoder
counting direction
and the motor positive rotation direction are the same.
- Make a Trajectory Move
To test that the motor is being driven properly, set up and execute
a small trapezoidal move.
Specify a small distance of (for example) 5,000 counts, and a low velocity
and acceleration of
(for example) 10,000, and 10 respectively. With a cycle time of 153
µsec, these values
correspond to roughly 997 counts/sec, and 6516 counts/sec2, respectively.
Whatever profile values you use, be sure that they are safe
for your system.
Here is the command sequence to use:
SetProfileMode 0 |
// Sets current profile mode to trapezoidal |
SetPosition 5000 |
// 5000 is the desired destination position |
SetVelocity 10000 |
// 10000 is the desired maximum velocity |
SetAcceleration 10 |
// 10 is the desired acceleration |
SetDeceleration 10 |
// 10 is the desired deceleration |
| Update |
// execute the move |
After entering this sequence of commands you should see the axis smoothly
move for about 6
seconds if the suggested values are used and the cycle time of the motion
processor is 153
µsec.
If you do not see the axis moving, or if the axis jumps rapidly in one
direction or the other, there
may be a problem with the board or software settings. Re-check and review
the setup
procedures, as well as the parameter settings.
When the initialization sequence is repeated, the results should be
consistent. If they are not
the initialization may not be correct. Re-check and contact PMD if problems
persist.
|
|